- Description
- Specifications
- Documents
FLUKE-1625-2 Earth Ground Tester
Features and Specifications
- 3- and 4-pole Fall-of-Potential, earth resistance loop testing
- 4-pole Soil Resistivity testing
- Selective earth ground rod testing using 1 clamp
- Stakeless earth ground rod testing using 2 clamps
- IP56 rated for outdoor use
- Rugged carrying case
- USB data storage and transfer
- Automatic Frequency Control (AFC) - identifies existing interference and chooses a measurement frequency to minimize its effect, providing more accurate earth ground value
- R* measurement – calculates earth ground impedance at 55 Hz to more accurately reflect the earth ground resistance that a fault-to earth ground would see
- Adjustable limits - for quicker testing
Stakeless Testing
The Fluke 1625-2 earth ground tester is able to measure earth ground loop resistances using only clamps. With this test method, two clamps are placed around the earth ground rod and each are connected to the tester. No earth ground stakes are used at all. A known, fixed voltage is induced by one clamp and the current is measured using the second clamp. Then the tester automatically determines the resistance of the earth ground rod. This test method only works if a bonded earth ground system exists for the building or structure under test, but most are. If there is only one path to ground, like at many residential applications, the Stakeless method will not provide an acceptable value and the Fall of Potential test method must be used.
With Stakeless testing, the earth ground rod does not need to be disconnected — leaving the bonded earth ground system intact during test. Gone are the days of spending time placing and connecting stakes for each earth ground rod on your system — a major time saver. You can also perform earth ground tests in places you've not considered before: inside buildings, power pylons, or anywhere you don't have access to soil.
The 1625-2 has advanced features, including automatic frequency control (AFC), which identifies existing interference and chooses a measurement frequency to provide more accurate values; R* measurement, which calculates earth ground impedance with 55 Hz to more accurately reflect the resistance that a fault-to-earth ground would experience; adjustable limits for quicker testing; and battery level status on the display.
The Fluke 1623-2 ia a unique earth ground tester that can perform all four types of earth ground measurement:
- 3- and 4-Pole Fall of Potential (using stakes)
- 4-Pole Soil Resistivity testing (using stakes)
- Selective testing (using 1 clamp and stakes)
- Stakeless testing (using 2 clamps only)
What's in the Box
- GEO Earth Ground Tester
- User's Manual
- Batteries
- Quick Reference Guide
- USB Cable